How to get a close loop transfer function from an open loop one?

200 views (last 30 days)
Hi all
The transfer function for my open loop system is
13.11 s^3 + 30.28 s^2 - 17650 s - 692.3
-------------------------------------------------
s^5 + 19.97 s^4 + 150.1 s^3 + 12.95 s^2 + 26.24 s
I wanted to know how to get the close loop equivalent of that transfer function above on MATLAB?
Kind regards

Accepted Answer

Sam Chak
Sam Chak on 12 Mar 2022
Assuming that the sensor measures perfectly (), then this is one of the ways:
s = tf('s');
G = (13.11*s^3 + 30.28*s^2 - 17650*s - 692.3)/(s^5 + 19.97*s^4 + 150.1*s^3 + 12.95*s^2 + 26.24*s)
H = 1;
Gcl = G/(1 + G*H) % closed-loop transfer function
Gcl = minreal(Gcl) % minimal order of Gcl
pole(Gcl) % find the poles of Gcl
ans =
-14.6294 + 0i
-6.1635 + 11.5538i
-6.1635 - 11.5538i
7.0258 + 0i
-0.0393 + 0i
Since one of the poles is in the right-half s plane, then the system is unstable. You will need to design a compensator to stabilize it.