Main Content

System-Level Heat Exchanger (2P-2P)

Heat exchanger based on performance data between two two-phase fluid networks

Since R2021b

  • System-Level Heat Exchanger (2P-2P) block

Libraries:
Simscape / Fluids / Heat Exchangers / Two-Phase Fluid

Description

The System-Level Heat Exchanger (2P-2P) block models a heat exchanger between two distinct two-phase fluid networks. Each network has its own set of fluid properties.

The block uses performance data from the heat exchanger datasheet, rather than the detailed geometry of the exchanger. Either or both sides of the heat exchanger can condense or vaporize fluid as a result of the heat exchange. You can also use this block as an internal heat exchanger in a refrigeration system. An internal heat exchanger improves refrigeration system efficiency by providing additional heat exchange between the outlet of the condenser and the outlet of the evaporator.

You parameterize the block by the nominal operating condition. The heat exchanger is sized to match the specified performance at the nominal operating condition at steady state.

Each side of the heat exchanger approximates the liquid zone, mixture zone, and vapor zone based on the change in enthalpy along the flow path.

Heat Transfer

The block divides the two-phase fluid 1 flow and the two-phase fluid 2 flow each into three segments of equal size and calculates heat transfer between the fluids is in each segment. For simplicity, the equation in this section are for one segment.

If you clear the Wall thermal mass check box, then the heat balance in the heat exchanger is

Qseg,2P1+Qseg,2P2=0,

where:

  • Qseg,2P1 is the heat flow rate from the wall that is the heat transfer surface to two-phase fluid 1 in the segment.

  • Qseg,2P2 is the heat flow rate from the wall to two-phase fluid 2 in the segment.

If you select Wall thermal mass, then the heat balance in the heat exchanger is

Qseg,2P1+Qseg,2P2=MwallcpwallNdTseg,walldt,

where:

  • Mwall is the mass of the wall.

  • cpwall is the specific heat of the wall.

  • N = 3 is the number of segments.

  • Tseg,wall is the average wall temperature in the segment.

  • t is time.

The heat flow rate from the wall to two-phase fluid 1 in the segment is

Qseg,2P1=UAseg,2P1(Tseg,wallTseg,2P1),

where:

  • UAseg,2P1 is the weighted-average heat transfer conductance for two-phase fluid 1 in the segment.

  • Tseg,2P1 is the weighted-average fluid temperature for two-phase fluid 1 in the segment.

The heat flow rate from the wall to the two-phase fluid 2 in the segment is

Qseg,2P2=UAseg,2P2(Tseg,wallTseg,2P2),

where:

  • UAseg,2P2 is the weighted-average heat transfer conductance for two-phase fluid 2 in the segment.

  • Tseg,2P2 is the weighted-average fluid temperature for two-phase fluid 2 in the segment.

Two-Phase Fluid 1 Heat Transfer Correlation

The block calculates the heat transfer conductance in both two-phase fluids by using the same expressions.

If the segment is subcooled liquid, then the heat transfer conductance is

UAseg,L,2P1=aL,2P1(Reseg,L,2P1)b2P1(Prseg,L,2P1)c2P1kseg,L,2P1G2P1N,

where:

  • aL,2P1, b2P1, and c2P1 are the coefficients of the Nusselt number correlation. These coefficients are block parameters in the Correlation Coefficients section.

  • Reseg,L,2P1 is the average liquid Reynolds number for the segment.

  • Prseg,L,2P1 is the average liquid Prandtl number for the segment.

  • kseg,L,2P1 is the average liquid thermal conductivity for the segment.

  • G2P1 is the geometry scale factor for the two-phase fluid 1 side of the heat exchanger. The block calculates the geometry scale factor so that the total heat transfer over all segments matches the specified performance at the nominal operating conditions.

The average liquid Reynolds number is

Reseg,L,2P1=m˙seg,2P1Dref,2P1μseg,L,2P1Sref,2P1,

where:

  • m˙seg,2P1 is the mass flow rate through the segment.

  • μseg,L,2P1 is the average liquid dynamic viscosity for the segment.

  • Dref,2P1 is an arbitrary reference diameter.

  • Sref,2P1 is an arbitrary reference flow area.

Note

The Dref,2P1 and Sref,2P1 terms are included in this equation for unit calculation purposes only, to make Reseg,L,2P1 nondimensional. The values of Dref,2P1 and Sref,2P1 are arbitrary because the G2P1 calculation overrides these values.

Similarly, if the segment is superheated vapor, then the heat transfer conductance is

UAseg,V,2P1=aV,2P1(Reseg,V,2P1)b2P1(Prseg,V,2P1)c2P1kseg,V,2P1G2P1N,

where:

  • aV,2P1, b2P1, and c2P1 are the coefficients of the Nusselt number correlation. These coefficients appear as block parameters in the Correlation Coefficients section.

  • Reseg,V,2P1 is the average vapor Reynolds number for the segment.

  • Prseg,V,2P1 is the average vapor Prandtl number for the segment.

  • kseg,V,2P1 is the average vapor thermal conductivity for the segment.

The average vapor Reynolds number is

Reseg,V,2P1=m˙seg,2P1Dref,2P1μseg,V,2P1Sref,2P1,

where μseg,V,2P1 is the average vapor dynamic viscosity for the segment.

If the segment is liquid-vapor mixture, then the heat transfer conductance is

UAseg,M,2P1=aM,2P1(Reseg,SL,2P1)b2P1CZ(Prseg,SL,2P1)c2P1kseg,SL,2P1G2P1N,

where:

  • aM,2P1, b2P1, and c2P1 are the coefficients of the Nusselt number correlation. These coefficients appear as block parameters in the Correlation Coefficients section.

  • Reseg,SL,2P1 is the saturated liquid Reynolds number for the segment.

  • Prseg,SL,2P1 is the saturated liquid Prandtl number for the segment.

  • kseg,SL,2P1 is the saturated liquid thermal conductivity for the segment.

  • CZ is the Cavallini and Zecchin term.

The saturated liquid Reynolds number is

Reseg,SL,2P1=m˙seg,2P1Dref,2P1μseg,SL,2P1Sref,2P1,

where μseg,SL,2P1 is the saturated liquid dynamic viscosity for the segment.

The Cavallini and Zecchin term is

CZ=((νseg,SV,2P1νseg,SL,2P11)(xseg,out,2P1+1))1+b2P1((νseg,SV,2P1νseg,SL,2P11)(xseg,in,2P1+1))1+b2P1(1+b2P1)(νseg,SV,2P1νseg,SL,2P11)(xseg,out,2P1xseg,in,2P1),

where:

  • νseg,SL,2P1 is the saturated liquid specific volume for the segment.

  • νseg,SV,2P1 is the saturated vapor specific volume for the segment.

  • xseg,in,2P1 is the vapor quality at the segment inlet.

  • xseg,out,2P1 is the vapor quality at the segment outlet.

The expression is based on the work of Cavallini and Zecchin [5], which derives a heat transfer coefficient correlation at a local vapor quality x. Equations for the liquid-vapor mixture are obtained by averaging Cavallini and Zecchin’s correlation over the segment from xseg,in,2P1 to xseg,out,2P1.

Two-Phase Fluid 1 Weighted Average

The two-phase fluid flow through a segment may not be entirely represented as either subcooled liquid, superheated vapor, or liquid-vapor mixture. Instead, each segment may consist of a combination of these. The block approximates this condition by computing weighting factors (wL, wV, and wM) based on the change in specific enthalpy across the segment and the saturated liquid and vapor specific enthalpies. The block assumes that the specific enthalpy across the segment varies piecewise linearly from inlet to outlet, with the breakpoints corresponding to the saturation boundaries for liquid and vapor. The zone with a larger heat transfer coefficient has a steeper slope than the zone with a lower heat transfer coefficient.

wL=ΔLΔL+ΔM+ΔVwV=ΔVΔL+ΔM+ΔVwM=1wLwV

ΔL=|min(hseg,out,2P1,hseg,SL,2P1)min(hseg,in,2P1,hseg,SL,2P1)|UAseg,M,2P1UAseg,V,2P1ΔM=|min(max(hseg,out,2P1,hseg,SL,2P1),hseg,SV,2P1)min(max(hseg,in,2P1,hseg,SL,2P1),hseg,SV,2P1)|UAseg,L,2P1UAseg,V,2P1ΔV=|max(hseg,out,2P1,hseg,SV,2P1)max(hseg,in,2P1,hseg,SV,2P1)|UAseg,L,2P1UAseg,M,2P1

where:

  • hseg,in,2P1 is the specific enthalpy at the segment inlet.

  • hseg,out,2P1 is the specific enthalpy at the segment outlet.

  • hseg,SL,2P1 is the saturated liquid specific enthalpy for the segment.

  • hseg,SV,2P1 is the saturated vapor specific enthalpy for the segment.

The weighted-average two-phase fluid 1 heat transfer conductance for the segment is therefore

UAseg,2P1=wL(UAseg,L,2P1)+wV(UAseg,V,2P1)+wM(UAseg,M,2P1).

The weighted-average fluid 1 temperature for the segment is

Tseg,2P1=wL(UAseg,L,2P1)Tseg,L,2P1+wV(UAseg,V,2P1)Tseg,V,2P1+wM(UAseg,M,2P1)Tseg,M,2P1UAseg,2P1,

where:

  • Tseg,L,2P1 is the average liquid temperature for the segment.

  • Tseg,V,2P1 is the average vapor temperature for the segment.

  • Tseg,M,2P1 is the average mixture temperature for the segment, which is the saturated liquid temperature.

Two-Phase Fluid 2 Heat Transfer Correlation

If the segment is subcooled liquid, then the heat transfer conductance is

UAseg,L,2P2=aL,2P2(Reseg,L,2P2)b2P2(Prseg,L,2P2)c2P2kseg,L,2P2G2P2N,

where:

  • aL,2P2, bL,2P2, and cL,2P2 are the coefficients of the Nusselt number correlation. These coefficients are block parameters in the Correlation Coefficients section.

  • Reseg,L,2P2 is the average liquid Reynolds number for the segment.

  • Prseg,L,2P2 is the average liquid Prandtl number for the segment.

  • kseg,L,2P2 is the average liquid thermal conductivity for the segment.

  • G2P2 is the geometry scale factor for the two-phase fluid 2 side of the heat exchanger. The block calculates the geometry scale factor so that the total heat transfer over all segments matches the specified performance at the nominal operating conditions.

The average liquid Reynolds number is

Reseg,L,2P2=m˙seg,2P2Dref,2P2μseg,L,2P2Sref,2P2,

where:

  • m˙seg,2P2 is the mass flow rate through the segment.

  • μseg,L,2P2 is the average liquid dynamic viscosity for the segment.

  • Dref,2P2 is an arbitrary reference diameter.

  • Sref,2P2 is an arbitrary reference flow area.

Note

The Dref,2P2 and Sref,2P2 terms are included in this equation for unit calculation purposes only, to make Reseg,L,2P2 nondimensional. The values of Dref,2P and Sref,2P2 are arbitrary because the G2P2 calculation overrides these values.

Similarly, if the segment is superheated vapor, then the heat transfer conductance is

UAseg,V,2P2=aV,2P2(Reseg,V,2P2)b2P2(Prseg,V,2P2)c2P2kseg,V,2P2G2P2N,

where:

  • aV,2P2, bV,2P2, and cV,2P2 are the coefficients of the Nusselt number correlation. These coefficients appear as block parameters in the Correlation Coefficients section.

  • Reseg,V,2P2 is the average vapor Reynolds number for the segment.

  • Prseg,V,2P2 is the average vapor Prandtl number for the segment.

  • kseg,V,2P2 is the average vapor thermal conductivity for the segment.

The average vapor Reynolds number is

Reseg,V,2P2=m˙seg,2P2Dref,2P2μseg,V,2P2Sref,2P2,

where μseg,V,2P2 is the average vapor dynamic viscosity for the segment.

If the segment is liquid-vapor mixture, then the heat transfer conductance is

UAseg,M,2P2=aM,2P2(Reseg,SL,2P2)b2P2CZ(Prseg,SL,2P2)c2P2kseg,SL,2P2G2P2N,

where:

  • aM,2P2, bL,2P2, and cL,2P2 are the coefficients of the Nusselt number correlation. These coefficients appear as block parameters in the Correlation Coefficients section.

  • Reseg,SL,2P2 is the saturated liquid Reynolds number for the segment.

  • Prseg,SL,2P2 is the saturated liquid Prandtl number for the segment.

  • kseg,SL,2P2 is the saturated liquid thermal conductivity for the segment.

  • CZ is the Cavallini and Zecchin term.

The saturated liquid Reynolds number is

Reseg,SL,2P2=m˙seg,2P2Dref,2P2μseg,SL,2P2Sref,2P2,

where μseg,SL,2P2 is the saturated liquid dynamic viscosity for the segment.

The Cavallini and Zecchin term is

CZ=((νseg,SV,2P2νseg,SL,2P21)(xseg,out,2P2+1))1+b2P2((νseg,SV,2P2νseg,SL,2P21)(xseg,in,2P2+1))1+b2P2(1+b2P2)(νseg,SV,2P2νseg,SL,2P21)(xseg,out,2P2xseg,in,2P2),

where:

  • νseg,SL,2P2 is the saturated liquid specific volume for the segment.

  • νseg,SV,2P2 is the saturated vapor specific volume for the segment.

  • xseg,in,2P2 is the vapor quality at the segment inlet.

  • xseg,out,2P2 is the vapor quality at the segment outlet.

The expression is based on the work of Cavallini and Zecchin [5], which derives a heat transfer coefficient correlation at a local vapor quality x. Equations for the liquid-vapor mixture are obtained by averaging Cavallini and Zecchin’s correlation over the segment from xseg,in,2P2 to xseg,out,2P2.

Two-Phase Fluid 2 Weighted Average

The two-phase fluid flow through a segment may not be entirely represented as either subcooled liquid, superheated vapor, or liquid-vapor mixture. Instead, each segment may consist of a combination of these. The block approximates this condition by computing weighting factors (wL, wV, and wM) based on the change in specific enthalpy across the segment and the saturated liquid and vapor specific enthalpies. The block assumes that the specific enthalpy across the segment varies piecewise linearly from inlet to outlet, with the breakpoints corresponding to the saturation boundaries for liquid and vapor. The zone with a larger heat transfer coefficient has a steeper slope than the zone with a lower heat transfer coefficient.

wL=ΔLΔL+ΔM+ΔVwV=ΔVΔL+ΔM+ΔVwM=1wLwV

ΔL=|min(hseg,out,2P2,hseg,SL,2P2)min(hseg,in,2P2,hseg,SL,2P2)|UAseg,M,2P2UAseg,V,2P2ΔM=|min(max(hseg,out,2P2,hseg,SL,2P2),hseg,SV,2P2)min(max(hseg,in,2P2,hseg,SL,2P2),hseg,SV,2P2)|UAseg,L,2P2UAseg,V,2P2ΔV=|max(hseg,out,2P2,hseg,SV,2P2)max(hseg,in,2P2,hseg,SV,2P2)|UAseg,L,2P2UAseg,M,2P2

where:

  • hseg,in,2P2 is the specific enthalpy at the segment inlet.

  • hseg,out,2P2 is the specific enthalpy at the segment outlet.

  • hseg,SL,2P2 is the saturated liquid specific enthalpy for the segment.

  • hseg,SV,2P2 is the saturated vapor specific enthalpy for the segment.

The weighted-average two-phase fluid 2 heat transfer conductance for the segment is therefore

UAseg,2P2=wL(UAseg,L,2P2)+wV(UAseg,V,2P2)+wM(UAseg,M,2P2).

The weighted-average fluid 2 temperature for the segment is

Tseg,2P2=wL(UAseg,L,2P2)Tseg,L,2P2+wV(UAseg,V,2P2)Tseg,V,2P2+wM(UAseg,M,2P2)Tseg,M,2P2UAseg,2P2,

where:

  • Tseg,L,2P2 is the average liquid temperature for the segment.

  • Tseg,V,2P2 is the average vapor temperature for the segment.

  • Tseg,M,2P2 is the average mixture temperature for the segment, which is the saturated liquid temperature.

Pressure Loss

The pressure losses on the two-phase fluid 1 side are

pA,2P1p2P1=K2P12m˙A,2P1m˙2A,2P1+m˙2thres,2P12ρavg,2P1pB,2P1p2P1=K2P12m˙B,2P1m˙2B,2P1+m˙2thres,2P12ρavg,2P1

where:

  • pA,2P1 and pB,2P1 are the pressures at ports A1 and B1, respectively.

  • p2P1 is internal two-phase fluid 1 pressure at which the heat transfer is calculated.

  • m˙A,2P1 and m˙B,2P1 are the mass flow rates into ports A1 and B1, respectively.

  • ρavg,2P1 is the average two-phase fluid 1 density over all segments.

  • m˙thres,2P1 is the laminar threshold for pressure loss, approximated as 1e-4 of the nominal mass flow rate. The block calculates the pressure loss coefficient, K2P1, so that pA,2P1pB,2P1 matches the nominal pressure loss at the nominal mass flow rate.

The pressure losses on the two-phase fluid 2 side are

pA,2P2p2P2=K2P22m˙A,2P2m˙2A,2P2+m˙2thres,2P22ρavg,2P2pB,2P2p2P2=K2P22m˙B,2P2m˙2B,2P2+m˙2thres,2P22ρavg,2P2

where:

  • pA,2P2 and pB,2P2 are the pressures at ports A2 and B2, respectively.

  • p2P2 is internal two-phase fluid 2 pressure at which the heat transfer is calculated.

  • m˙A,2P2 and m˙B,2P2 are the mass flow rates into ports A2 and B2, respectively.

  • ρavg,2P2 is the average two-phase fluid 2 density over all segments.

  • m˙thres,2P2 is the laminar threshold for pressure loss, approximated as 1e-4 of the nominal mass flow rate. The block calculates the pressure loss coefficient, K2P2, so that pA,2P2pB,2P2 matches the nominal pressure loss at the nominal mass flow rate.

Two-Phase Fluid 1 Mass and Energy Conservation

The mass conservation equation for the overall two-phase fluid 1 flow is

(dp2P1dtsegments(ρseg,2P1p)+segments(duseg,2P1dtρseg,2P1u))V2P1N=m˙A,2P1+m˙B,2P1,

where:

  • ρseg,2P1p is the partial derivative of density with respect to pressure for the segment.

  • ρseg,2P1u is the partial derivative of density with respect to specific internal energy for the segment.

  • useg,2P1 is the specific internal energy for the segment.

  • V2P1 is the total two-phase fluid 1 volume.

The summation is over all segments.

Note

Although the block divides the two-phase fluid 1 flow into N=3 segments for heat transfer calculations, it assumes all segments are at the same internal pressure, p2P1. Consequentially, p2P1 is outside of the summation.

The energy conservation equation for each segment is

duseg,2P1dtM2P1N+useg,2P1(m˙seg,in,2P1m˙seg,out,2P1)=Φseg,in,2P1Φseg,out,2P1+Qseg,2P1,

where:

  • M2P1 is the total two-phase fluid 1 mass.

  • m˙seg,in,2P1 and m˙seg,out,2P1 are the mass flow rates into and out of the segment.

  • Φseg,in,2p1 and Φseg,out,2p1 are the energy flow rates into and out of the segment.

The block assumes the mass flow rates between segments are linearly distributed between the values of m˙A,2P1 and m˙B,2P1.

Two-Phase Fluid 2 Mass and Energy Conservation

The mass conservation equation for the overall two-phase fluid 2 flow is

(dp2P2dtsegments(ρseg,2P2p)+segments(duseg,2P2dtρseg,2P2u))V2P2N=m˙A,2P2+m˙B,2P2,

where:

  • ρseg,2P2p is the partial derivative of density with respect to pressure for the segment.

  • ρseg,2P2u is the partial derivative of density with respect to specific internal energy for the segment.

  • useg,2P2 is the specific internal energy for the segment.

  • V2P2 is the total two-phase fluid 2 volume.

The summation is over all segments.

Note

Although the block divides the two-phase fluid 2 flow into N=3 segments for heat transfer calculations, it assumes all segments are at the same internal pressure, p2P2. Consequentially, p2P2 is outside of the summation.

The energy conservation equation for each segment is

duseg,2P2dtM2P2N+useg,2P2(m˙seg,in,2P2m˙seg,out,2P2)=Φseg,in,2P2Φseg,out,2P2+Qseg,2P2,

where:

  • M2P2 is the total two-phase fluid 2 mass.

  • m˙seg,in,2P2 and m˙seg,out,2P2 are the mass flow rates into and out of the segment.

  • Φseg,in,2p2 and Φseg,out,2p2 are the energy flow rates into and out of the segment.

The block assumes the mass flow rates between segments are linearly distributed between the values of m˙A,2P2 and m˙B,2P2.

Ports

Output

expand all

Rate of heat transfer to the first two-phase fluid network, returned as a physical signal, in W. The physical signals at ports Q1 and Q2 are usually equal in value with opposite sign. However, if you select Wall thermal mass, then these two signals may have different values because the wall may absorb and release some of the heat being transferred.

Rate of heat transfer to the second two-phase fluid network, returned as a physical signal, in W. The physical signals at ports Q1 and Q2 are usually equal in value with opposite sign. However, if you select Wall thermal mass, then these two signals may have different values because the wall may absorb and release some of the heat being transferred.

Conserving

expand all

Inlet or outlet port associated with the first two-phase fluid network.

Inlet or outlet port associated with the first two-phase fluid network.

Inlet or outlet port associated with the second two-phase fluid network.

Inlet or outlet port associated with the second two-phase fluid network.

Parameters

expand all

Configuration

Flow path alignment between the heat exchanger sides at nominal operating condition. The available flow arrangements are:

  • Counter flow - Two-Phase Fluid 1 flows from A to B, Two-Phase Fluid 2 flows from B to A — The flows run parallel to each other, in the opposite directions.

  • Parallel flow - Both fluids flow from A to B — The flows run in the same direction.

  • Cross flow - Both fluids flow from A to B — The flows run perpendicular to each other.

The choice between parallel flow and counter flow affects how the block determines the size of the heat exchanger. The counter flow setting is the most effective, and needs the smallest size to meet the specified performance. Conversely, parallel flow is the least effective, and needs the biggest size to meet the specified performance.

Flow direction at the nominal condition (from A to B, or from B to A) only affects the model initialization, when you select Initialize two-phase fluid 1 to nominal operating conditions or Initialize two-phase fluid 2 to nominal operating conditions. If you set different initial operating conditions, the flow directions can be different.

After the block determines the size of the heat exchanger, this setting does not play a role in how the block calculates the heat transfer during simulation. Instead, the heat transfer depends on the flow directions during simulation. For example, if you set the parameter to parallel flow but set up the model to run in counter flow, then the rate of heat transfer during simulation will not match the specified performance, even if the rest of the boundary conditions are the same.

If you set the parameter to cross flow, then the block models the flow paths as perpendicular inside the heat exchanger, so the flow directions during simulation do not matter.

Whether to enable the effect of thermal mass on the heat transfer surface. When you select this parameter, the block introduces additional dynamics to the simulation and takes longer to reach steady state, but this parameter does not affect the results at steady-state simulation.

Mass of the heat transfer surface.

Dependencies

To enable this parameter, select Wall thermal mass.

Specific heat of the heat transfer surface.

Dependencies

To enable this parameter, select Wall thermal mass.

Option to initialize the wall temperature to nominal operating conditions or specified values. If you select this parameter, the block calculates the initial wall temperature from the nominal operating conditions specified for both fluid sides. If you clear this parameter, you can specify the initial wall temperature directly with the Initial wall temperature parameter.

Dependencies

To enable this parameter, select Wall thermal mass.

Initial temperature of the wall. If you specify a scalar, the block assumes that the initial wall temperature is uniform. If you specify a two-element vector, then the block assumes that the initial wall temperature varies linearly between ports A1 and A2 and ports B1 and B2. The first element corresponds to the temperature at ports A1 and A2 and the second element corresponds to the temperature at ports B1 and B2.

Dependencies

To enable this parameter, select Wall thermal mass and clear the Initialize wall temperature to nominal operating conditions check box.

Flow area at the two-phase fluid 1 port A1.

Flow area at the two-phase fluid 1 port B1.

Flow area at the two-phase fluid 2 port A2.

Flow area at the two-phase fluid 2 port B2.

Two-Phase Fluid 1

Nominal operating condition:

  • Heat transfer from Two-Phase Fluid 1 to Two-Phase Fluid 2 — Side 1 is cooled and side 2 is heated.

  • Heat transfer from Two-Phase Fluid 2 to Two-Phase Fluid 1 — Side 2 is cooled and side1 is heated.

This setting relates only to the nominal operating condition parameters. It does not mean that heat transfer can only happen in the specified direction during simulation.

Mass flow rate from port A1 to port B1 during the nominal operating condition.

Pressure drop from port A1 to port B1 during the nominal operating condition.

Select the method of pressure specification:

  • Inlet pressure — Specify the nominal inlet pressure.

  • Saturation pressure at specified saturation temperature — Specify the nominal saturation temperature.

Pressure at the two-phase fluid 1 inlet of the heat exchanger during nominal operating condition.

Dependencies

To enable this parameter, set Pressure specification to Inlet pressure.

Saturation temperature at the two-phase fluid 1 outlet of the heat exchanger during nominal operating condition. The pressure in the heat exchanger is the corresponding saturation pressure. The nominal saturation temperature must be less than the critical temperature.

Dependencies

To enable this parameter, set Pressure specification to Saturation pressure at specified saturation temperature.

Quantity used to describe the inlet condition of the fluid at the nominal operating condition: temperature, specific enthalpy, or vapor quality.

Specific enthalpy at the two-phase fluid 1 inlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Inlet condition specification to Specific enthalpy.

Temperature at the two-phase fluid 1 inlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Inlet condition specification to Temperature.

Vapor quality, defined as the mass fraction of vapor in a liquid-vapor mixture, at the two-phase fluid 1 inlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Inlet condition specification to Vapor quality.

Whether to specify the performance of the heat exchanger for two-phase fluid 1 at the nominal operating condition directly, by the rate of heat transfer, or indirectly, by the outlet condition.

Rate of heat transfer. The Nominal Operating condition parameter determines the network that the heat transfers from and to:

  • If Nominal operating condition is Heat transfer from two-phase fluid 1 to two-phase fluid 2, this parameter is the rate of the heat transfer from the two-phase fluid side 1 to side 2 during the nominal operating condition.

  • If Nominal operating condition is Heat transfer from two-phase fluid 2 to two-phase fluid 1, this parameter is the rate of the heat transfer from the two-phase fluid side 2 to side 1 during the nominal operating condition.

Dependencies

To enable this parameter, set Heat transfer capacity specification to Rate of heat transfer.

Select the quantity for outlet condition specification:

  • Specific enthalpy — Specify the nominal specific enthalpy.

  • Subcooling — Specify the nominal subcooling. This option is available if you set Nominal operating condition to Heat transfer from two-phase fluid 1 to two-phase fluid 2.

  • Superheating — Specify the nominal superheating. This option is available if you set Nominal operating condition to Heat transfer from two-phase fluid 2 to two-phase fluid 1.

  • Vapor quality — Specify the nominal vapor quality.

Dependencies

To enable this parameter, set Heat transfer capacity specification to Outlet condition.

Specific enthalpy at the two-phase fluid 1 outlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Outlet condition specification to Specific enthalpy.

Degree of temperature below the liquid saturation temperature at the two-phase fluid 1 outlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Outlet condition specification to Subcooling.

Degree of temperature above the vapor saturation temperature at the two-phase fluid 1 outlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Outlet condition specification to Superheating.

Two-phase fluid vapor quality, defined as the mass fraction of vapor in a liquid-vapor mixture, at the two-phase fluid 1 outlet of the heat exchanger during the nominal operating condition.

If using this option, the initial pressure cannot be higher than the critical pressure.

Dependencies

To enable this parameter, set Outlet condition specification to Vapor quality.

Total volume of two-phase fluid 1 inside the heat exchanger.

Option to initialize the two-phase fluid to nominal operating conditions or specified values. If you select this parameter, the block initializes the two-phase fluid to the nominal operating conditions. If you clear this check box, you can specify the initial conditions directly with additional parameters.

Quantity used to describe the initial state of the side 1 fluid: temperature, vapor quality, vapor void fraction, specific enthalpy, or specific internal energy.

The value for Initial fluid energy specification parameter limits the available initial states for the two-phase fluid. When Initial fluid energy specification is:

  • Temperature — Specify an initial state that is a subcooled liquid or superheated vapor. You cannot specify a liquid-vapor mixture because the temperature is constant across the liquid-vapor mixture region.

  • Vapor quality — Specify an initial state that is a liquid-vapor mixture. You cannot specify a subcooled liquid or a superheated vapor because the liquid mass fraction is 0 and 1, respectively, across the whole region. Additionally, the block limits the pressure to below the critical pressure.

  • Vapor void fraction — Specify an initial state that is a liquid-vapor mixture. You cannot specify a subcooled liquid or a superheated vapor because the liquid mass fraction is 0 and 1, respectively, across the whole region. Additionally, the block limits the pressure to below the critical pressure.

  • Specific enthalpy — Specify the specific enthalpy of the fluid. The block does not limit the initial state.

  • Specific internal energy — Specify the specific internal energy of the fluid. The block does not limit the initial state.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box.

Two-phase fluid 1 pressure at the start of the simulation.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box.

Two-phase fluid 1 specific enthalpy at the start of simulation. If the value is a scalar, then the initial specific enthalpy is assumed uniform. If the value is a two-element vector, then the initial specific enthalpy is assumed to vary linearly between ports A1 and B1, with the first element corresponding to port A1 and the second element corresponding to port B1.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box and set Initial fluid energy specification to Specific enthalpy.

Two-phase fluid 1 temperature at the start of simulation. If the value is a scalar, then the initial temperature is assumed uniform. If the value is a two-element vector, then the initial temperature is assumed to vary linearly between ports A1 and B1, with the first element corresponding to port A1 and the second element corresponding to port B1.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box and set Initial fluid energy specification to Temperature.

Two-phase fluid 1 vapor quality, defined as the mass fraction of vapor in a liquid-vapor mixture, at the start of simulation. If the value is a scalar, then the initial vapor quality is assumed uniform. If the value is a two-element vector, then the initial vapor quality is assumed to vary linearly between ports A1 and B1, with the first element corresponding to port A1 and the second element corresponding to port B1.

If using this option, the initial pressure cannot be higher than the critical pressure.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box and set Initial fluid energy specification to Vapor quality.

Two-phase fluid 1 vapor void fraction, defined as the volume fraction of vapor in a liquid-vapor mixture,at the start of simulation. If the value is a scalar, then the initial vapor void fraction is assumed uniform. If the value is a two-element vector, then the initial vapor void fraction is assumed to vary linearly between ports A1 and B1, with the first element corresponding to port A1 and the second element corresponding to port B1.

If using this option, the initial pressure cannot be higher than the critical pressure.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box and set Initial fluid energy specification to Vapor void fraction.

Two-phase fluid 1 specific internal energy at the start of simulation. If the value is a scalar, then the initial specific internal energy is assumed uniform. If the value is a two-element vector, then the initial specific internal energy is assumed to vary linearly between ports A1 and B1, with the first element corresponding to port A1 and the second element corresponding to port B1.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 1 to nominal operating conditions check box and set Initial fluid energy specification to Specific internal energy.

Two-Phase Fluid 2

Mass flow rate from port A2 to port B2 during the nominal operating condition.

Pressure drop from port A2 to port B2 during the nominal operating condition.

Select the method of pressure specification:

  • Inlet pressure — Specify the nominal inlet pressure.

  • Saturation pressure at specified saturation temperature — Specify the nominal saturation temperature.

Pressure at the two-phase fluid 2 inlet of the heat exchanger during nominal operating condition.

Dependencies

To enable this parameter, set Pressure specification to Inlet pressure.

Saturation temperature at the two-phase fluid 2 outlet of the heat exchanger during nominal operating condition. The pressure in the heat exchanger is the corresponding saturation pressure. The nominal saturation temperature must be less than the critical temperature.

Dependencies

To enable this parameter, set Pressure specification to Saturation pressure at specified saturation temperature.

Quantity used to describe the inlet condition of the fluid at the nominal operating condition: temperature, specific enthalpy, or vapor quality.

Specific enthalpy at the two-phase fluid 2 inlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Inlet condition specification to Specific enthalpy.

Temperature at the two-phase fluid 2 inlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Inlet condition specification to Temperature.

Vapor quality, defined as the mass fraction of vapor in a liquid-vapor mixture, at the two-phase fluid 2 inlet of the heat exchanger during the nominal operating condition.

Dependencies

To enable this parameter, set Inlet condition specification to Vapor quality.

Total volume of two-phase fluid 2 inside the heat exchanger.

Option to initialize the two-phase fluid to nominal operating conditions or specified values. If you select this parameter, the block initializes the two-phase fluid to the nominal operating conditions. If you clear this check box, you can specify the initial conditions directly with additional parameters.

Quantity used to describe the initial state of the side 2 fluid.

The value for Initial fluid energy specification parameter limits the available initial states for the two-phase fluid. When Initial fluid energy specification is:

  • Temperature — Specify an initial state that is a subcooled liquid or superheated vapor. You cannot specify a liquid-vapor mixture because the temperature is constant across the liquid-vapor mixture region.

  • Vapor quality — Specify an initial state that is a liquid-vapor mixture. You cannot specify a subcooled liquid or a superheated vapor because the liquid mass fraction is 0 and 1, respectively, across the whole region. Additionally, the block limits the pressure to below the critical pressure.

  • Vapor void fraction — Specify an initial state that is a liquid-vapor mixture. You cannot specify a subcooled liquid or a superheated vapor because the liquid mass fraction is 0 and 1, respectively, across the whole region. Additionally, the block limits the pressure to below the critical pressure.

  • Specific enthalpy — Specify the specific enthalpy of the fluid. The block does not limit the initial state.

  • Specific internal energy — Specify the specific internal energy of the fluid. The block does not limit the initial state.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box.

Two-phase fluid 2 pressure at the start of the simulation.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box.

Two-phase fluid 2 specific enthalpy at the start of simulation. If the value is a scalar, then the initial specific enthalpy is assumed uniform. If the value is a two-element vector, then the initial specific enthalpy is assumed to vary linearly between ports A2 and B2, with the first element corresponding to port A2 and the second element corresponding to port B2.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box and set Initial fluid energy specification to Specific enthalpy.

Two-phase fluid 2 temperature at the start of simulation. If the value is a scalar, then the initial temperature is assumed uniform. If the value is a two-element vector, then the initial temperature is assumed to vary linearly between ports A2 and B2, with the first element corresponding to port A2 and the second element corresponding to port B2.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box and set Initial fluid energy specification to Temperature.

Two-phase fluid 2 vapor quality, defined as the mass fraction of vapor in a liquid-vapor mixture, at the start of simulation. If the value is a scalar, then the initial vapor quality is assumed uniform. If the value is a two-element vector, then the initial vapor quality is assumed to vary linearly between ports A2 and B2, with the first element corresponding to port A2 and the second element corresponding to port B2.

If using this option, the initial pressure cannot be higher than the critical pressure.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box and set Initial fluid energy specification to Vapor quality.

Two-phase fluid 2 vapor void fraction, defined as the volume fraction of vapor in a liquid-vapor mixture,at the start of simulation. If the value is a scalar, then the initial vapor void fraction is assumed uniform. If the value is a two-element vector, then the initial vapor void fraction is assumed to vary linearly between ports A2 and B2, with the first element corresponding to port A2 and the second element corresponding to port B2.

If using this option, the initial pressure cannot be higher than the critical pressure.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box and set Initial fluid energy specification to Vapor void fraction.

Two-phase fluid 2 specific internal energy at the start of simulation. If the value is a scalar, then the initial specific internal energy is assumed uniform. If the value is a two-element vector, then the initial specific internal energy is assumed to vary linearly between ports A2 and B2, with the first element corresponding to port A2 and the second element corresponding to port B2.

Dependencies

To enable this parameter, clear the Initialize two-phase fluid 2 to nominal operating conditions check box and set Initial fluid energy specification to Specific internal energy.

Correlation Coefficients

Proportionality constant in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for subcooled liquid in two-phase fluid 1. The default value is based on the Colburn equation.

Proportionality constant in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for liquid-vapor mixture in two-phase fluid 1. The default value is based on the Cavallini and Zecchin correlation.

Proportionality constant in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for superheated vapor in two-phase fluid 1. The default value is based on the Colburn equation.

Reynolds number exponent in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for two-phase fluid 1. The same value applies to subcooled liquid, liquid-vapor mixture, and superheated vapor.

Prandtl number exponent in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for two-phase fluid 1. The same value applies to subcooled liquid, liquid-vapor mixture, and superheated vapor.

Proportionality constant in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for subcooled liquid in two-phase fluid 2. The default value is based on the Colburn equation.

Proportionality constant in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for liquid-vapor mixture in two-phase fluid 2. The default value is based on the Cavallini and Zecchin correlation.

Proportionality constant in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for superheated vapor in two-phase fluid 2. The default value is based on the Colburn equation.

Reynolds number exponent in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for two-phase fluid 2. The same value applies to subcooled liquid, liquid-vapor mixture, and superheated vapor.

Prandtl number exponent in the correlation of the Nusselt number as a function of the Reynolds number and Prandtl number for two-phase fluid 2. The same value applies to subcooled liquid, liquid-vapor mixture, and superheated vapor.

References

[1] Ashrae Handbook: Fundamentals. Atlanta: Ashrae, 2013.

[2] Çengel, Yunus A. Heat and Mass Transfer: A Practical Approach. 3rd ed. McGraw-Hill Series in Mechanical Engineering. Boston: McGraw-Hill, 2007.

[3] Mitchell, John W., and James E. Braun. Principles of Heating, Ventilation, and Air Conditioning in Buildings. Hoboken, NJ: Wiley, 2013.

[4] Shah, R. K., and Dušan P. Sekulić. Fundamentals of Heat Exchanger Design. Hoboken, NJ: John Wiley & Sons, 2003.

[5] Cavallini, Alberto, and Roberto Zecchin. “A DIMENSIONLESS CORRELATION FOR HEAT TRANSFER IN FORCED CONVECTION CONDENSATION.” In Proceeding of International Heat Transfer Conference 5, 309–13. Tokyo, Japan: Begellhouse, 1974. https://doi.org/10.1615/IHTC5.1220.

Extended Capabilities

C/C++ Code Generation
Generate C and C++ code using Simulink® Coder™.

Version History

Introduced in R2021b

expand all