Why can I not set the ranges properly for the CIO-DAS16/JR block in xPC Target 2.7.2 (R14SP2)?
1 view (last 30 days)
Show older comments
I cannot seem to be able to set the ranges properly for the CIO-DAS16/JR block in xPC Target 2.7.2 (R14SP2). The ranges listed in the mask do not match the actual ranges.
Accepted Answer
MathWorks Support Team
on 27 Jun 2009
This bug has been fixed in Release 14 Service Pack 3 (R14SP3). For previous product releases, read below for any possible workarounds:
We have verified that there is a bug in xPC Target 2.7.2 (R14SP2) in that the "Range vector" in the block parameters of the Measurement Computing CIO-DAS16/JR block has one extra entry that the board does not support.
To work around this issue, use the following two lists to pick the menu entry that will give you your desired range.
Menu Actual Range
---- ------------
+-10 +-10
+-5 +-5
+-2.5 +-2.5
+-1.25 +-1.25
+-0.625 0-10
0-10 0-5
0-5 0-2.5
0-2.5 0-1.25
0-1.25 XX Does not work XX
0 Comments
More Answers (0)
See Also
Categories
Find more on Target Computer Setup in Help Center and File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!