I want to model 100KVA load operating at 0.9 power factor lagging. What should i set Active Power, QL and QC in load parameters?
5 views (last 30 days)
Show older comments
Syed Umaid Ali
on 29 Sep 2020
Commented: Syed Umaid Ali
on 29 Sep 2020
Hi,
Please help me find the answer to this question:
I want to model 100KVA load operating at 0.9 power factor lagging. What should i set Active Power, QL and QC in load parameters?
0 Comments
Accepted Answer
Pemendra Kumar Pardhi
on 29 Sep 2020
as per your requirement
Apparent power S= √(P^2+Q^2 ).....................................(1)
And power factor Cosφ= 0.9 lagging, i.e. only inductive load(QL=.. and Qc=0);
Where ϕ= tan^-1(Q/P),.....................................................(2)
from Eq. 1 and 2 you can obtained value of P and QL